Pages

Monday, June 26, 2017

How small ignorance could cause huge damage in APH of boiler


Hello!! all the power plant professionals,today we will discuss about causes of AHP fire and precautions need to be taken to avoid such mishaps and after that I will share one of the real incident of APH fire which I have witnessed then you will come to know that how it could be disastrous.Function of APH is to increase temperature of air supplied to boiler by recovering waste heat from flue gas to increase overall thermal efficiency of boiler.Installation of APH helps in following ways to boiler;

  • Increase in thermal efficiency of boiler as most of the waste heat is absorbed by air from flue gas.
  • Increase in temperature of air stabilises ignition and improves combustion efficiency of boiler.
  • Decrease in fuel consumption and also make it possible to use low grade fuel.
  • Helps in increase in steam generation capacity and gives stability during load fluctuations.

These are the advantages of APH but when things are going in wrong direction then it could be harmful to both man and machine.

Now causes of APH fire are as follows,

  • The important reason for APH fire is continues accumulation of unburnt fuel fines in gaps of tubes or surrounding duct area;when that accumulated unburnt fuel gets favourable conditions for secondary combustion it starts burning in that area and causes APH fire.
  • Maintaining low excess air supply for combustion in furnace; which is ultimately responsible for insufficient amount of Oxygen for combustion and resulting in improper combustion in furnace and results in carry over of unburnt fuel along with flue gas to 2nd  pass duct and will accumulate and may catch fire.
  • Due to air ingress from leakage in flue gas passing duct there will be sudden drop in temperature of flue gas and moisture in flue gas gets condensed and water droplets will forms and resulting in stagnant condition for  particles in the flue gas and will get accumulated and when suitable conditions occurs it may catch fire.
  • Maintaining improper furnace pressure which will restrict  flue gas flow and causes accumulation of unburnt in APH and surrounding duct and may catch fire when it gets proper resources for burning.
  • If ash handling system for APH is not working properly then hoppers will get full and it may catch fire if it gets.

To avoid APH fire precautions need to be taken are as follows;
  • Maintain sufficient amount of excess air for complete combustion of fuel in furnace i.e.try to maintain proper O2 at the time of operation of boiler.
  • Find any leakage in duct and arrest them as soon as possible.
  • Try to maintain proper negative furnace pressure for free flow of flue gas.
  • Check ash handling systems on regular basis.

If suppose there will be fire in APH then ,How to identify it. There are several conditions which are pointing out towards APH fire while normal operation as follows;
  • Rise in temperature of air at APH outlet than normal operating conditions.
  • Sudden rise in temperature of flue gas after APH.
  • Rise in temperature of flue gas at Super heater.
  • Increase in opening of steam temperature controlling attemperator control valves.
  • Rise in casing plate temperature from outside.May be checked with temp measuring gun.
Now we will discuss about one of such incident of APH fire which I have witnessed.

This incident I have faced when I was commissioning boiler.Before explaining  actual incident I will tell History in brief.So commissioning of boiler was in its last phase i.e steam blowing ,we were giving steam blow downs as per procedure by the gap of 2 hours with targate plate at its position.And finally at 6:00 pm after 77 steam blows we got clear targate plate upon which turbine personal and customer side manger agreed and signed protocols. So now we all have decided to stop boiler at 7:30 pm so that we can wrap up balanced erection work  as soon as possible to start it again for commercial steam generation.So boiler has stopped by shutting fuel feeding of and and told operator to keep all the fans in running condition till all the temperatures inside boiler comes down to around 5C and we left site at 8:00 pm. But in the name of hurry to leave plant operator stop all the fans at 9:00 pm and by mistake left SA fan in running condition and left plant . When next shift person came and he also hasn't checked that APH temp is rising.Now at around 11:45 pm when we reached plant and found that temperature of APH risen so high that APH tubes started melting and outer casing warped due to heat and protective aluminium sheet also melted.And in control room we found only SA fan running ;immediately I have started all the fans and keep them running for cooling of boiler.  



Melted outer Aluminium cladding sheet





Melted APH tubes clicked from menhole


In night we were not able to identify intensity  of damage done and APH outlet temperature found reached to 550 C. And after cutting outer casing plate we found the real damage as shown below,


Damaged APH section of boiler

Almost 6000 no of tubes found damaged.After analysis and investigation we come to conclusion that this thing was happened due to accumulation of unburnt fuel in between gap of APH tubes. Amount of moisture in fuel was high because which fuel was not burning properly and carried over to APH section and accumulated over there. After stopping boiler slowly moisture in the fuel got veporized and dry fuel starts burning as all the fans were stopped before sufficient reduction in temperature of boiler. And natural draft created due to ID fan provided air for combustion and unburnt fuel catches fire.But fortunately half of the section saved due SA fan was running because APH was divided in two sections i.e. SA APH and PA APH .As SA fan was running air was carrying heat along with it and saved metal of tubes from getting overheated.As PA fan was not running PA APH tubes got overheated and melted.

Saved section of SA APH

So I am suggesting all the power plant professionals that be alert on small signals because it could cause sever damage afterwards.Follow all the instructions given above to prevent such incident to be happened in your plant.

Hope this article will help you all ,feel free to ask and if you have any suggestion always welcome.Please subscribe and follow blog as a motivation for more such important articles.

Saturday, June 24, 2017

Important Stages in Commissioning and Stabilization of Power Plant


Hello!! All the power plant professionals .When we talk about any plant it generally has to go through three main phases throughout its lifespan i.e. mechanical Erection of plant, Commissioning and Operation and maintenance of plant. Normally we talk about operation and maintenance of plant but commissioning is also a very important phase as in this phase plant has to start first time, so we need to take special precautions before starting plant. There are various checklists, protocols and SOP’s need to follow in commissioning of plant. So today here we will discuss about various stages involved in commissioning and stabilisation of plant. Here  I have categorised different stages and sequence of performing. Important stages involved in commissioning are as follows,

  1. Mechanical erection completion of plant.
  2. Hydraulic test of pressure part
  3. Duct leakage test on flue gas side
  4. No load trail of motors
  5. Trail run of rotating equipment
  6. Refractory dry out
  7. Alkali boil out
  8. Safety valve floating
  9. Steam Blowing
  10. Commercial steam generation
  11. Performance guarantee test
So now here we will discuss different stages one by one in detail in terms purpose, care to be taken and procedure in general.

1. Mechanical erection completion of plant

After given clearance from erection team regarding completion of erection, we need to inspect different things from commissioning point of view like quality of weld at tube joints and various channel sections, alignment of weld and water wall panel ,position and tension in various supports provided, room for expansion of tubes and steam line etc as per P&ID .After finding everything satisfying go for next step which is Hydraulic test.

            2. Hydraulic test of pressure part

Hydraulic test in a Boiler is carried out to check leakages of pressure parts and prove the strength of the Boiler at a pressure greater than the working pressure of the boiler, and is carried out at following stages:
  •  On completion of erection.
  •  On completion of repair of Boiler pressure parts.
  •  On completion of Annual overhaul of pressure parts.
  • At the request of Authority to full fill the statutory requirement.
Care to be taken
  •  Boiler should be at room temperature condition.
  •  Water used for hydraulic test must be as near as possible to the temperature of the boiler pressure parts temperature & if there is difference in temperature then it should not be more than 50 deg C.
  •  Maintain quality of boiler water as per operation manual or maintain pH between 8.5 to 10.5 & Hydrazine to approximately 200 ppm.
  •  Boiler must be hydro tested to 1.5 Times of design pressure only for first time test after completion of erection as per Regulatory requirement.
  •  All valves provided on the drains and for instrument isolation shall be completely closed.
  •  Vent valves shall be kept open to purge the air pocket while filling and to be closed after the air pockets are purged.
  •  Before applying pressure, the unit shall be examined to see that all valves & gasket joints are tight and no leakage is observed.
Procedure
  •  The pressure shall be gradually raised to the test pressure with the help of Hydraulic pump preferably 1-1.5 kg/cm2 per minute. The relief valve provided on the leak off line of the pump shall be operated to control the rate of pressure rising. After raising the boiler pressure to test value, the isolation valve at unit inlet shall be closed.
  •  The unit shall be held under test pressure for maximum 30 minutes. Quick inspection for leakage/sweating shall be carried out during these 30 minutes. The pressure shall be then reduced to maximum allowable working pressure and maintained at that pressure while the unit is carefully examined for leakage. Depressurise it also with rate of 1-1.5 kg/cm2 per minute
  •  Leaks through welds, castings, forging, plate, pipe and tubes excluding gasket joints are not acceptable. Seepage at the test pressure is permitted only at gasket joints.

           3. Leakage test of furnace or combustor and second pass duct

To make system leak proof, there is need of Leak test inside combustor, air and flue gas path after completion of all mechanical works, included sealing and fin welding. If not done there will be leakages of air and flue gas during operation and which costs in terms of  loss in efficiency of boiler, Load restriction , ID fan overload, cold air ingress.

Care to be taken
  • Leakage testing of all ducting is preferably done with smoke.
  •  Extra care should be taken while performing  Air pre-heater Leak test
  •  Sealing of roof should be examined carefully.
  •  Marking should be done at leakage prone area for attending it later.
  •  Carry out repair with good engineering practice
  •  All fins and seal welding completed as per drawing.
  •  All openings such as manholes, SA nozzles, view holes & Instrument pockets are installed and sealed properly.
  •  Grid nozzles area to be dummied with help of tape or tarpaulin sheet.
  •  Volume to be tested is to be decided by site engineer, based on number of smoke generator machines available and accordingly areas are to be blanked with temporary arrangements.

Procedure
  • For leak test first requirement is to seal the area where test will be done.
  •  After sealing put smoke generator inside and start the machine.
  •  Smoke will spread inside and make full of smoke.
  •  If any fan or blower is available and testing area can be pressurized then start it and take adequate pressure.
  •  After this check all the area from outside anywhere smoke coming. If not then OK, if any leakage found, repair it in proper manner and again do the leak test.
  •  This process will be repeated until no leakage is ensured.
  • For every segment, testing area will be decided by site team as per machines availability and sealing of how much area can be done at once.

          4. No load trail of motors

No load trail of motor is to be done after installing motor at position and without coupling keep it in running condition for 4 hrs and note down parameters on hourly basis to test its reliability before taking it in actual operation.

          5. Trail run of rotating equipments

 After completion of no load trail of motors then motors are coupled with respective rotating i.e. pump, fan etc. After coupling equipment stared at lowest minimum load possible and gradually taken to full load and again reduced to lowest possible load. While increasing load parameters like current, rpm, damper opening etc noted down to compare with factory provided data of equipment. This activity is performed to test reliability of whole equipment and after completion of test clearance is given for starting boiler for further activities. 

        6. Refractory dry out (RDO) test

A newly erected boiler, or one on which extensive furnace refractory repairs have been carried out will require to be dried out thoroughly before commissioning the boiler.  The procedure is to allow control drying out of wet brickwork and refractory to the lowest rate of heating possible for avoiding the separation or cracking. Thermal stresses will be produced if heating rate is too rapid. From this it follows that LONGER PERIOD OF LOW TEMPERATURE DRYING CAUSES MORE EVEN HEAT DISTRIBUTION RESULTING IN BETTER REFRACTORY DRY OUT.
If not done cracking or separation of refractory may occur. Pressure parts may face thermal shocks.

Care to be taken

In deciding initial heating temperature and its duration the following factors should be considered:
  • Estimated moisture content of walls and refractory.
  • Thickness of walls and refractory.
  • The distance from heat source.
  • Strict follow up of drying curve as per in operation manual.
  •  Ensure the availability of adequate feed water as per recommended quality.
  •  Quantity of fuel required to be estimated as per the capacity and type of boiler.
  •  Ensure the readiness of draught system and required Instrumentation for boiler firing.
Procedure
  • Fill boiler with specified water approximately 50 mm below of normal water level is showing in water gauge glass (approx. 1/3 of gauge glass).
  •  Open start up vent valve initially 20% and then adjust after lit up as per operating condition
  •  Start required drives (Fans, Pumps etc) for combustion and draught control.
  •  Lit up the boiler. After fire is established, set air to maintain draft & combustion.
  •  Increase slowly the heat input to boiler to raise the pressure & Soaking is to be given as per the heating curve.
  •  At a pressure of approximately 2.1 Kg /cm2, the drum air release valves are to be shut.
  •  Control the fires & gradually raise furnace temperature and maintain soaking time & temperature as per the heating curve during the activity. The variation in soaking temperature is allowed up to ± 10 deg C.
  •  After completion of refractory dry out, stop fans.  Allow boiler to cool down naturally once the fire is extinguished.

         7. Alkali Boil Out

To remove oil, grease and other foreign particle a newly erected boiler, or one on which extensive repairs to pressure parts have been carried out, may have an oil or grease film on internal areas which is impossible to remove fully by manual cleaning. Since oil and grease have a very low rate of heat transfer, tubes contaminated by these, can be overheated when subjected to high temperatures. This will lead to blistering or burning of the tube metal with consequent risk of rupture. Chemical cleaning of boiler pressure parts is carried out to overcome the above problems. If not done then Oil, Grease has very low heat transfer coefficient, if not removed they can hindrance in local heat transfer thus tube failure may occur.

Care to be taken
  • Chemicals used must never be poured in solid form, but at first to be dissolved in water and then poured in to the boiler system.
  • Alkali boil out is carried in Two stages : Atmospheric boil out at low pressure for pre cleaning followed by pressure boil out at 75% of working pressure or 40 kg/cm2 whichever is less.
  • The solution is formulated by dissolving the following proportionate quantities for Atmospheric boil out.

     0.05% Na2PO4.7H2O  (500 PPM disodium phosphate)
        0.1% Na3PO4.12H2O  (1000 PPM tri sodium phosphate)
                                                Surfactant (Washing powder) 10 to 20 PPM to reduce surface tension.
  • The  atmospheric boil out is carried for 12 hours giving blow downs from all header and drum drains every two hours.
  • The solution is formulated by dissolving the following proportionate quantities for pressure boil out
     0.05% Na2PO4.7H2O  (500 PPM disodium phosphate)
        0.05% Na3PO4.12H2O  (500 PPM tri sodium phosphate)
                      Surfactant (Washing powder) 10 to 20 PPM to reduce surface tension


Risk: if chemical poured and feed pump got failed or any heavy leakage occurred or any other interruption occurred, then you have to maintain furnace temperature more than 2000C in any case, otherwise chemical to be drained out.
  •  Pressure boil out is declared complete when oil level in sample falls Below 5 ppm or after a minimum of 12 hours.
       Final inspection after chemical boil out: 
  • After rinsing, drain the boiler completely; cut the inspection caps of all the bottom headers (as per engineering instruction).
  • When boiler has cooled down open all manhole doors to allow inspection of all internal surfaces.
  • Open the steam drum & water drum manholes, clean drum with wire brush and DM water and remove the sediments, accumulated dirt and sludge (if any).
  • Examine all internal baffles and check the tightness of all fittings, also the internal pipe work etc.
  • After completion of the rinsing & cleaning of all bottom headers, inspect all bottom headers for any unwanted particle with help of light/torch and clearance can be given for end cap welding.
  • If water gauge glass has got fouled in boiling out, these must be dismantled and cleaned as per maker’s instructions.
  • Re-weld the end caps on headers as per the recommended procedures.
  • Examine all external heating surfaces and gas passes of boiler for excessive soot deposits resulting from low firing rates employed in boiling out. Clean manually the soot deposits.
       Care to be taken 
  •       Required temperature should be maintained through out the process at all stages.
  •       If in any case interruption occurred and activity can not be carried out then acid cleaning circuit to be flushed properly with DM water after chemical draining immediately.
  •       Its effluent should be drained at proper place like effluent pond or drain trench.
  •       During acid cleaning upto 1st stage passivation it should be ensured that the system always remained filled with solution, if there is any partial draining required simultaneously DM water should be filled up, so that any open air cannot be contact with boiler tube surface.
  •       Monitor the return lines temperature by temperature gauge to ensure the flow through each circuit.

              8. Safety valve floating

      
       Setting the safety valves to the designed set pressures before allowing the boiler to go for commercial steaming.

      Set Pressure
      This is the pressure at which the valve begins to lift from the valve seat.

      Full lift pressure
      This is the pressure at which the valve reaches its fully open position. 

      Closing Pressure
      Closing pressure is the pressure at which the valve reseats.
      
      Blow down %
      The blow down is the difference between the set pressure and the closing pressure expressed as a percentage of the set pressure e.g.

      Blow down % = Set pressure-Closing pressure x100
                                              Set pressure

      And is usually in order of 2 ½   to 4 ½ .
      
      Sequence of setting  

       Drum 1-  Drum 2 - Superheater 
    
     
      Care to be taken
  • Safety valve exhaust pipe support to be checked
  • Silencer support to be checked
  •  Safety valve flange bolts  proper tightening with metallic gasket
  •  Drip pan drain line connection
  •  safety valve body vent and drain to be extended upto safe zone
  • Drip pan pipe peripheral gap checking for expansion purpose
  •  Drip pan top cover plate to be kept free
  • Safety valve cold assembly to be checked
  • Prior to floating boiler maximum pressure to be raised to check thermal expansion in all area of Boiler.
  • Hand popping to be done before safety valve floating
  • Check Start up vent control valve to be smooth in operation for safety valve floating. 

      Setting the safety Valves
  
      This operation involves increasing and decreasing heat input to the boiler, to raise and lower the steam pressure. The set pressure and closing pressure of each valve is checked and adjusted in turn from the highest-pressure valve first to the lowest pressure last.
  • Steam flow through super heater must be maintained and controlled at an   adequate rate through operation of super heater drain / startup vent valve
  •  Raise steam pressure slowly to set pressure for first safety valve.
  •  Raise the boiler pressure upto set pressure/full lift pressure. When the valve pops, cut off fire and open start up vent valve. Restore drum level.
  •  When the sound of escaping steam is heard note pressure reading on calibrated gauge. Note pressure again when full lift point is reached.
  •  Allow pressure to fall and note pressure at which safety valve resets (Closing pressure).
  • The set pressure is adjusted by either tightening or loosening the adjusting nut. Tightening of the nut increases the set pressure and vice versa.
  •  If noted pressures are not as specified, then adjustments must be made and the process of checking repeated until correct reading is obtained.
  •  During the test a close watch must be kept on drum water level, as steam will     be lost at each lift of the safety valves as well as through the continuous discharge from the super heater drain/startup vent.  Control the feed to   compensate for these losses.
  •  Repeat test for each safety valve in descending order of set pressures. 

The valve, which was already set, should be left ungaged.

 image source:google                                    Safety valve

      9. Steam Blowing

       The Purpose of steam blowing is to de-scale and remove foreign materials from steam pipelines leading to turbine in order to avoid damage to turbine blades from such material in the course of normal operation. If not done then Damage to turbine blades from such material in the course of normal operation.

Principle
  • Steam Blowing is carried out by Puffing Method for main steam line to Turbine. 
  •  Steam Blowing is carried out by Continuous blow Method for low and medium pressure lines to process plants/ Deaerator.
  •  Dislodge rust/scales from pipe work by thermal shocks.
  •  High momentum of expanding steam in the pipe work purges out the loosened material.
  •  It is required to create a higher momentum during steam blowing than possible during operation of the unit. This is applicable for all steam piping leading to turbine.
  •  Care to be taken to terminate the discharge to a safer place
  •  Steam blowing completion criteria to be discussed & decided as per the application of steam.  

            Care to be taken

       Steam blowing temporary arrangement with MOV operated sacrificing valve and target plate assembly to be erected with proper support.
       Main Steam line supports to be checked.
       All drain lines to be checked for not choked and clear during line hydro test
       Attemperator control valve to be made ready
      Sacrificing valve ,MSSV and its bypass operation to be checked from DCS.
  Steam blowing procedure and target plate acceptance criteria to be finalized with all concerned.
       Feed pump and feed water control station should be ready for normal operation
                    Drum level and pressure transmitters to be properly calibrated.

Steam Blowing by Puffing method:
  • Lit up Boiler as per procedure and raise the pressure upto 15 kg/cm2.First blow will be given at 15 kg/cm2 by opening sacrificing valve as quick as possible and after completion of blow check the blowing line and its support. 2-3 blows initially will be given on 15-20 kg/cm2. After these initial blows raise the pressure upto 75% working pressure or 40 kg/cm2 whichever maximum.
  •  Maintain Drum level to 50 % of gauge glass & then open gradually the Main Steam Stop Valve fully and charge the line to the inlet of the closed sacrificing valve. Minimize the firing rate to maintain the drum level. The super heater drain should now be closed.
  •  Open the sacrificing valve as fast as possible and keep it open till the boiler pressure falls down to 40 % of the working pressure or a pressure drop of 10 kg/cm2 whichever is lower . Now close the sacrificing valve. Once the sacrificing valve close completely, close Main steam stop valve. Open the drain line valves to depressurize the line. After depressurizing the line, open the sacrificing valve fully to cool down the line.
  •  Maintain at least 2 hour time gap between two consecutive steam blows.
  •  Repeat the above steam blowing exercise several times as long as you could visually observe the steam blowing is clear. Now, isolate MSSV and insert soft metal target plate in the holder provided in temporary piping. Increase Boiler Pressure up to 75 % of its working Pressure, limited to a maximum of 40 kg/cm2. Repeat the blowing one time with the target plate.  Close MSSV and remove target plate. If target plate is not clean, repeat steam-blowing cycle for 3 to 4 times without target plate. Then fix target plate in its predetermined position and then again give steam blows till the target plate is found clear. Target plate will be checked as per the acceptance criteria and upon acceptance, the steam blowing is said to be completed. 
         Steam Blowing by continuous method:
  •  Lit up Boiler as per procedure and raise the pressure upto 15 kg/cm2.First blow will be given at 15 kg/cm2 by opening sacrificing valve as quick as possible and after blow check the blowing line and its support. 2-3 blows initially will be given on 15-20 kg/cm2. After these initial blows raise the pressure upto 75% working pressure or 40 kg/cm2 whichever maximum.
  •  Maintain Drum level to 55 % of gauge glass & then open gradually the Main Steam Stop valve fully and charge the line to the inlet of the line to be blown.
  •  Open gradually the valve at the inlet of the line to be blown keeping a close watch on drum level and firing rate to maintain the pressure. Open the valve till the flow is achieved equivalent to the design flow of this line. Boiler main steam flow meter can be utilized to monitor the flow. If the flow is below 30% MCR of the boiler flow, keep the start up vent open to maintain at least 30% flow thru the boiler. Keep this condition for about ONE hour and then close the valve for allowing the line to cool down.
  •  Maintain at least 2 hour time gap between two consecutive steam blows.
  •  Repeat the above steam blowing exercise several times as long as you could visually observe the steam blowing is clear. Now, isolate MSSV and insert soft metal target plate in the holder provided for temporary piping. Increase Boiler Pressure up to 75 % of its working Pressure, limited to a maximum of 40 kg/cm2. Repeat the blowing one time with the target plate.  Close MSSV and remove target plate. If target plate is not clean, repeat steam-blowing cycle for 3 to 4 times without target plate. Then fix target plate in its predetermined position and then again give steam blows till the target plate is found clear. Target plate will be checked as per the acceptance criteria and upon acceptance, the steam blowing is said to be completed.
             
             10. Commercial steam generation:

              After steam blowing completed and target plate clearance given by turbine or customer personal then we are ready to generate steam on commercial basis as per requirement.

             11. Performance guarantee test
  • PG test is not only limited to the efficiency test of the boiler, PG test is type of protocol regarding various parameters decided at the time of contract finalization.
  • PG test Procedure is prepared as per contract and the Code Requirement.
  • Have a pre test MOM with Client. Jointly calibrate the instruments
  • Conduct the test at site i.e. run plant at full capacity for 4 hrs continuously and noting down parameters after every half an hour.
  • Signed log sheets after completion of test.
  • Need to prepare a report and submit to client along with a contractual letter


         After completion of PG test satisfactorily ,plant is completely handed over to client and he      is responsible for further operation of plant.


Hope we have discussed enough on commissioning of power plant. And for any quires feel free to contact and suggestions always welcome.


Thursday, June 22, 2017

Mechanisms of Boiler tube leakage

Hello!! power plant engineers. The failure of industrial boiler has been a prominent feature in fossil fuel power plants. The contribution of one or several factors appears to be responsible for failures, eliminating in the partial or complete shutdown of the plant resulting in heavy losses in industrial production and disruption to civil amenities. The use of inferior tube materials, use of high sulphur or/and vanadium containing fuels, exceeding the design limit of temperature and pressure during operation, poor maintenance and ageing are some of the factors which have a detrimental effect on the performance of materials of construction. The failure of boiler tubes appeared in the form of bending, bulging, Wearing or rupture, decarburization, carburization causing leakage of the tubes. The failure can be caused by one or more modes such as overheating, Stress Corrosion Cracking, hydrogen embrittlement, creep, flame impingement, sulphide attack, weld attack, dew point attack, hot corrosion, etc.

Failure of boiler water side components during operation may not only be costly from an operations and personnel perspective, but potential legal costs may well outstrip the actual physical costs. It is incumbent upon the system designer, the builder, the operators and the chemical treatment supplier to ensure that the systems will operate reliably. When this happens, a full assessment of the failure mechanisms is required to preclude further failures due to the same factors. Several failure modes are addressed in this article, which hopefully will give the boiler engineers a better understanding of failure analysis and failure mitigation.
Tube failures are classified as in-service failures in boilers. These failures can be grouped under five major causes:

  1. Stress rupture
  2. Water side corrosion
  3. Fatigue
  4. Erosion
  5. Fire side corrosion (also called as High temperature Corrosion)

1. STRESS RUPTURE


1.1 OVERHEATING:

Tube failures occur due to the ‘Overheating’ and the ‘Plastic Flow’ conditions associated with restricted flow of water in side of the particular tube facing failure.
Such failures are generally of two types:

  A)   Short term Overheating 
  B)   Long term Overheating

Careful examination of the failed tube section reveals whether the failure is on account of rapid acceleration in the tube wall temperature or it is on account of a long term gradual build up/ accumulation of the cause of failure.

A) Short Term Over-Heating:

Short term overheating failures frequently exhibits a thin- lipped longitudinal rupture, accompanied by noticeable tube bulging, which creates the large fish-mouth appearance as shown in fig. Virtually all types of tubes, which carry water or steam and are exposed to high operating temperatures, are susceptible to these types of failure. The more violent ruptures occur at tube metal operating temperature well above the ASME  oxidation limits of the material and typically above the eutectoid transformation temperature  7270 C. Peak metal operating temperatures above the can be estimated by  the amount  of bainite or martensite mixed with ferrite in the metal micro-structure at the failure origin. When conditions causing a rapid metal temperature elevation at local spot occur, a violent rupture results. The ‘Plastic – Flow’ phenomena of ‘Carbon Steel’ materials at temperatures between: 700 0C – 800 0C is the cause of such occurrences.


Interruption/ Restriction, in the water circulation by some blockage in tube leads to such failures, as the tube metal gets exposed to direct flames in such cases. Short term failures can be caused by low water level partial or complete plugging of tubes, rapid start up, excessive load swings and excessive heat input.

B) Long Term Over-Heating:

‘Long Term’ conditions finally lead to a tube leak; wrinkled or bulged external surfaces are observed in such cases. Such appearance is caused by long term ‘Creep Failure’ causing by repetitive scale formation, which leads to ‘Overheating’, thus ‘Swelling’ the surface, forming a Bulge or Blister, visually observable minor fissures, etc. on external surfaces. Long term failures mainly occurs in super heaters, reheaters and water walls as a result of gradual accumulation of deposits or scale, partially restricted steam or water flow, excessive heat input from burners or undesired  channelising of fireside gases. Horizontal or inclined tubes subjected to steam blanketing are also prone to long term failures. Tube metal operating temperatures above 4540 C, or slightly above the oxidation limits of tube steels, can lead to blistering, tube bulging or thick lipped creep rupture failures.
It is recommended that the quality of the ‘Boiler Feed Water’ for boilers operating at 21 Kg/ cm2   (g) should be as per the annexure ‘A’ attached herewith. It is also recommended that the ‘Blow down Time’ & duration should be observed as per the annexure ‘B’ attached herewith. Blow Down must also be conducted on regular basis (When Boiler is in Low Steaming Stage) from side wall, rear & front wall headers; so that sludge accumulation in these headers may be avoided; which otherwise would rise in furnace tubes creating conditions for circulation restrictions/ blockage, thus overheating at local spots.

                 At times, foreign matters get left behind during the erection. Such happenings may be avoided by carefully examining tubes/ headers after fitting the same by a suitable method, such as, ball test/ by passing water & observing flow at the other end (where possible). Anyhow, these precautions should be taken before the firing of the Boiler.

ANNEXURE ‘A’

Sr.
Feed Water



1
Hardness, Max. (as Ca CO3)           mg/L
:
10
2
pH at 25 0C                                                            
:
8.8 to 9.2
3
Oxygen, Max.                                   mg/L
:
0.01
4
Total Iron                                          mg/L
:
0.100
5
Copper, Max.                                    mg/L
:
0.05
6
Total Dissolved Solids, Max.           mg/L
:
200

Sr.
Boiler Water



1
pH at 25 0C
:
9.8 to 10.8
2
Phosphate Residual (as PO4)                           mg/L
:
20 to 40 (If Added)
3
Total Dissolved Solids, Max. (T.D.S.)             mg/L
:
3500
4
Conductivity at 25 0C, Max.     Microsiemens/ cm
:
7000
5
Total Alkalinity                                                mg/L
:
700













1.2 DISSIMILAR METAL WELDS:

Designers of boiler Super heater/Reheater pendents incorporate the favorable mechanical properties of stainless steel within these sections of the boiler that combine high heat and high gas flows. However, due to the high material costs, these sections are ultimately welded to more common low alloy steels. This resulting dissimilar metal welds (DMW’s) have a tendency to suffer service related deteriorations (cracking) over time. Cracking of dissimilar metal welds is typically attributed to three primary factors.

The most significant factor is the difference between the thermal coefficient of expansion of ferrite, representing the low-alloy steel tubing, and austenite, representing the stainless steel weld deposit and tubing. This difference results in a significant temperature-induced stress at the weld interface.

The second factor contributing to the degradation of this type of weld is carbon diffusion from the ferrite to the austenite. This diffusion occurs slightly during welding and more extensively during subsequent use in high temperature service. It leaves a band of carbon depleted low-alloy steel immediately adjacent to the weld interface. This band of low-alloy steel has a much lower resistance to creep than average, and as a result has a greater propensity for failure by creep.

The third factor affecting the integrity of this type of weld is a difference in oxidation resistance between low alloy and stainless steels. This difference results in an oxide wedge forming along the outside and inside diameters of the component in question at the interface between these two materials. These wedges will continue to grow as a result of the difference in the oxidation resistance of the two materials. The oxide wedges reduce the available cross sectional thickness of the component, and thus, its load bearing capacity.


2.  WATER SIDE CORROSION


2.1 HYDROGEN DAMAGE

          Hydrogen damage occurs in boilers operating usually above 70 kg/cm2 and under heavy deposits or other areas where corrosion releases atomic hydrogen. Concentrated sodium hydroxide beneath the deposits removes the protective magnetite film by the following reactions:

                                         4 NaOH   +   Fe3O4     →      2 NaFeO2   +   Na2FeO2   +  2H2O


Concentrated sodium hydroxide can then react with freshly exposed base metal to yield sodium ferroate and atomic hydrogen 

                                                         Fe    +     2NaOH     →    Na2FeO2    +   2H

Upsets in phosphate treatment programs or residual acids from chemical cleanings can also cause hydrogen damage, especially if the acids remain trapped beneath the deposits. These failures are typically characterised as thick lipped, brittle type ruptures. Sometimes thick walled “windows” can be completely blown out of the tube wall.

2.2 CAUSTIC GOUGING:              

             Sodium hydroxide (NaOH) is used extensively in boiler water treatment to maintain the optimum hydroxyl ion concentration range to form a protective magnetite film on steel surfaces and to help from non adherent sludge when hardness enters the boiler water. However, excessive sodium hydroxide can destroy the protective film and corrode the base metal as shown in equations. NaOH can concentrate during departure from nucleate boiling (DNB), film boiling or steam blanketing conditions.Concentration also occurs when normal boiler water evaporates beneath deposits leaving behind the caustic at the metal surface. The effect of tube metal gouging beneath deposits.

Caustic gouging can also occur due to evaporation along a water line without significant accumulation of deposit as shown in fig in theses case, solubilized sodium ferroite is removed from the base tube metal, but then hydrolyzes and precipitates elsewhere in the boiler as magnetite when the concentrated water is diluted by normal boiler water.

2.3 OXYGEN ATTACK:

The presence of dissolved oxygen in boiler water causes the cathode of any corrosion cell to depolarize, thereby sustaining the corrosion process. Formation of reddish brown hermatite (Fe2O3) or “rust” deposits or tubercles accomplished by hemispherical pitting is the most familiar form of oxygen attack.

Dissolved oxygen is also a significant component in ammonia corrosion of copper alloys, stress concentration cracking austenitic stainless steels and Chelan corrosion.  Oxygen pitting occurs with the presence of excessive oxygen in boiler water. It can occur during operation as a result of in leakage of air at pumps, or failure in operation of pre-boiler water treatment equipment. This also may occur during extended out-of-service periods, such as outages and storage, if proper procedures are not followed in lay-up. Non-drainable locations of boiler circuits, such as super heater loops, sagging horizontal super heater and repeater tubes, and supply lines, are especially susceptible. More generalized oxidation of tubes during idle periods is sometimes referred to as out-of-service corrosion. Wetted surfaces are subject to oxidation as the water reacts with the iron to form iron oxide. When corrosive ash is present, moisture on tube surfaces from condensation or water washing can react with elements in the ash to form acids that lead to a much more aggressive attack on metal surfaces.

2.4  Stress Corrosion Cracking (SCC):

Stress Corrosion Cracking (SCC) is a cracking process that requires the simultaneous action of a corrodent and sustained tensile stress. In relation to boilers this problem was formerly called caustic embrittlement. Stress corrosion cracking is often confused with corrosion fatigue and has been observed in both the steam and mud drums of boilers. If there is seepage between the tube and drum it is possible for the concentration of NaOH to increase dramatically in this area. Metallurgically, the drum under load is in tensile loading and with a high localised caustic concentration, the ideal environment is produced for SCC. Although the incidence of SCC was found to be low it is known that there were several major problems in 70bar petrochemical boilers. To prevent SCC in the best way is to prevent the concentration of corrosion compounds either mechanically or chemically through appropriate maintenance and water treatment respectively.
                                                                              

3.  FATIGUE

As fatigue is such an important feature and the various mechanisms are quite distinct, it has been split into the three most common types, namely Thermal, Corrosion and Mechanical Fatigue. From experience it is known that thermal and corrosion fatigue are common occurrences, particularly with fire-tube boilers.

3.1 THERMAL FATIGUE

Thermal fatigue is defined as fracture resulting from the presence of temperature gradients that vary with time in such a manner as to produce cyclic stresses in the structure. Thermal fatigue occurs when metal is subjected to a number of rapid heating and cooling cycles causing large differences in thermal expansion between the structural members. Depending on the magnitude of the thermal shock involved, failure can occur with less than ten cycles. The material in question is normally in a condition of high restraint. Biaxial or triaxial stresses are induced in the affected surface producing micro cracks on the surface of the material. Once initiated then crack will continue to propagate with each cycle. In fire tube boilers the most common cause is internal scale, which prevents sufficient heat transfer and hence adequate cooling. Over-firing, incorrect burner settings and too many on/off cycles are amongst common causes resulting in cracking. In water tube boilers thermal fatigue can occur when there is frequent wetting of a hot surface such as is caused by an ill placed and leaking valve dripping internally into a hot steam line. Such failure of a steam line could have very serious consequences. Thermal fatigue cracks can be similar to corrosion fatigue and the two are often confused. Thermal fatigue can only be eliminated by removing the offending thermal cycling. Thermal fatigue damage typically exhibits numerous and crazing.
This damage results from cyclic and excessive temperature gradients can accomplished by mechanical constrains. Excessive temperature can add to internal strain to initiate or enhance the cracking process. Once initiated, freshly exposed metal within the cracks can undergo oxidation. Creating a wedge effect at the crack tip, since the oxide occupies a greater volume than a base metal .Thermal fatigue can occur in water walls or other areas subjected to DNB or rapidly fluctuating flows. Low amplitude vibrations of entire super heaters can lead to thermal fatigue 

3.2 Corrosion fatigue:

Corrosion fatigue is defined as cracking produced under the combined action of fluctuating stress and a corrosive environment at lower stress levels or frequencies than would be required in the absence of a corrosive environment. Corrosion fatigue in boilers is extremely dangerous and is the subject of many treatises. It requires the interaction of cyclic loading, corrosive environment and a high residual stress field. Several failures have resulted in considerable loss of life. As with thermal fatigue it manifests itself in quite different forms in fire-tube and water-tube boilers. A weld undercut, corrosion pit or other defect, usually at the toe of the weld, could cause the high stress. The joint area is usually in high restraint. The first phase of the initiation is the cracking of the protective oxide layer by the cyclic loading. This permits fresh attack by the corrosive medium on the bare metal and the formation of micro cracks. The exposed metal at the root of the crack is oxidized and then cracks at the next cycle so propagating the failure. Cracks are distinctively wedge shaped and transgranular particularly in the early stages. Most of the water tube boilers that were found to exhibit corrosion fatigue were in the higher Pressure range. The appearance of these defects is typical of corrosion fatigue but there may also have been a contribution from caustic embrittlement, also known as stress corrosion cracking (SCC).
                                                       


3.3 Mechanical fatigue:

 Mechanical fatigue can be defined as fracture under fluctuating mechanical stresses having a maximum value less than the ultimate tensile strength of the material.


Mechanical fatigue is what most people imagine when the word 'fatigue' is mentioned. Several instances in water tube boilers have been encountered where cracking has occurred in the tube to manifold weld of drainable super heaters. This was due to the vibration from inadequately supported elements. This is an often-neglected part of boiler maintenance. Other failures, again from vibration, have been due to defective tube-to-tube welds a result of manufacturing defects.

3.4 Flow assisted corrosion:

Flow assisted corrosion (FAC) is the localized thinning of a component related to the dissolution of the protective oxide film and the underlying base metal. The mechanisms involved in FAC are very complex due to the effect of many variables, which influences its occurrence. In utility operations FAC is typically seen in single or two phase water flowing in carbon steel piping. The more common locations where FAC is detected are:

  • ·         Low pressure system blends in evaporators, risers and economizer
  • ·         Feed water cycle (due to more volatile chemistry and lower pH)

There are essentially seven variables which affect FAC: with those to
  1. ·         Temperature
  2. ·         pH
  3. ·         Oxygen concentration
  4. ·         Mass flow rate
  5. ·         Geometry
  6. ·         Quality of fluid (single or two phase)
  7. ·         Materials of construction


4. EROSION

4.1 Fly Ash Erosion:

In most countries, fly ash erosion (FAE) is the most serious or second cause of availability loss for fossil plants. Historically the approach has been to arbitrarily position solid shields and baffles or apply a variety of coatings in ‘areas’ where FAE was occurring. It was recognized in an earlier study that the use of these palliative repair techniques was the main cause of repeat failures due to fly ash erosion. They simply redirected the high velocity flow onto an adjacent tube area.

 The rate and extent of erosive processes are affected by particle velocity, angle of impact, particle composition and shape, and erosive resistance of the tube surface including composition and temperature variations. Particle velocity is the most important parameter as the rate of erosive loss is proportional to the velocity raised to an exponent that ranges between two and four. Particle velocity is driven by the local flow velocity at any particular boiler location. The optimum long term solutions are based on identifying and reducing the highest velocity locations. It is important to note that local velocities, not bulk velocities across a section of the boiler are those of interest. As a rule of thumb, maximum design bulk velocities are on the order of 50 ft/sec or less. It has been observed that local velocities in excess of 100 ft/sec are required to cause fly ash erosion failures in 10,000 to 50,000 hours. The primary tool to combat FAE is flow modification in conjunction with a cold air velocity test before and after modification. A comprehensive EPRI Guideline has been published since the last conference, which provides a stepby- step procedure. This overall approach is shown in Figure  Where units have been evaluated by the cold air velocity technique (CAVT) to determine local velocity profiles, maximum local velocities of two or more times the nominal velocity have typically found, and these peak velocities usually correspond to the locations of know tube erosion damage.

              The use of CAVT to identify regions of excessive velocity, followed by the installation of diffusion and distribution screens, should provide utilities with the most permanent solution to the problem. However, the technique has not been adopted by sufficient utilities, which explains why FAE is still the second most important failure mechanism.

5. FIRE SIDE CORROSION

Corrosion on the fire side of boiler tubes is caused by moisture condensing from the atmosphere during periods of shutdown, or from flue gas condensation during operation. This type of corrosion is especially troublesome in boiler installations near bodies of water, or where the atmosphere is otherwise humid. Fire side corrosion is accelerated by the use of high sulfur fuels. Sulfur gases may condense on tube surfaces during operation; depending upon the kind of fuel, its sulfur content and the methods of firing. Accumulations of soot on the tubes should be periodically removed. Soot attracts moisture; and air, moisture and steel together result in attack of the tubes. Cleaning may be daily, weekly or monthly, depending on the fuel used and the method of firing.

Some hot water boilers -- for example, those in greenhouses -- may operate at water temperatures of 140oF to 150oF. Under such conditions, the condensing gases from coal or oil firing form sulfurous acid which attacks the tubes and results in a more uniform type of corrosion. If the percentage of sulfur in the fuel is high, this situation is worse. Even in the absence of sulfur compounds, corrosion may occur during shutdown periods because of high humidity in the air. When shutting down the boiler under such conditions, the fire side tube surfaces should be brushed and flushed to remove the winter's accumulation of soot and other products of combustion. This should be followed by blowing air through to dry out these surfaces. A light coat of oil should be applied for further protection. Also, in extremely humid locations, the stack should be disconnected, or at least the damper should be closed, and a tray of unslaked lime placed in the ash pit to keep the fire side dry. This lime must be renewed whenever it becomes mushy, so the drying effectiveness will not be lost. Many samples of scale removed from fire side surfaces have been found to be acid when mixed with water. The presence of this acid may cause the tube metal to eat away to eventual failure. Often, boiler rooms are in damp cellars, some with water on the floor constantly. During the summer months, in particular, humid air tends to build up in basements, causing clothes and leather to mildew from the dampness. Similarly, humid air may have ready access to the fire side of boiler tubes in basement installations if the tubes are not properly protected.
Even with gas firing of hot water boilers, serious fire side attack can take place. Some installations employ outdoor-indoor thermometers to control system water temperatures as outdoor temperatures fluctuate. Low water temperatures can result in condensation of moisture from the flue gas and lead to serious corrosion of the tubes. High water temperatures reduce the probability of attack.

Some horizontal tube boilers suffer from a mechanism called "necking" and "grooving."
This shows up as a circumferential groove around the outside of the tube where it enters the tube sheet. It usually occurs at the beginning of the first pass, which is the hottest end of the tubes. In all cases, there is some corrosion in evidence in other areas, but it concentrates at the ends because of strains from two sources. When tubes are rolled in, some unavoidable expansion takes place back of the tube sheet. Secondly, when a boiler heats up, the metal in the tubes expands and lengthens. Consequently, strains are set up at the ends, which are fixed in the tube sheets. Sometimes these expansions are so severe that the tubes loosen in the sheets. Scale forming at the tube ends tends to flake off, exposing fresh steel to further attack. This problem can be reduced by more gradual firing, more gradual changes in temperature, and maintaining the boiler water free of oxygen and under proper control.

From above discussion we come to conclusion that for minimizing such type of failures use some safety precautions as stated in operation & maintanance manual. Don't forgot to share experiences and views.